产品简介
P F报警设定器KFD2-WAC2-EX1.D冠宁科技16年专业做工控
P F报警设定器KFD2-WAC2-EX1.D冠宁科技16年专业做工控
产品价格:¥300.00
上架日期:2025-11-27 04:27:20
产地:上海上海
发货地:上海上海
供应数量:不限
最少起订:1
浏览量:8
资料下载:暂无资料下载
其他下载:暂无相关下载
详细说明
    产品参数
    信号类型数字输入
    开关点2.1 毫安
    安全完整性等级SIL 2
    线路故障检测断裂0.1 mA
    连接端子14
    连接输出端子7
    额定电压103
    输出二端子8
    功率耗散1 W
    开关电压40 V
    最大功耗1.5 W
    开关电流100 mA
    端子1
    信号10 mA
    开路电压8 V DC

    Connectionterminals 1 , 2-, 3 , 4-, 5 , 6-
    Lead resistancemax. 25 Ω per line
    Input I
    Connectionterminals 1 , 2-
    Sensor supply1 ... 5 V
    Connectionterminals 3 , 4- (supply); 5 , 6- (signal)
    Short-circuit current50 mA
    Load≥ 116 Ω up to 5V, ≥ 85 Ω up to 4V



    Connection sidecontrol side
    ConnectionOutput I: terminals 10, 11, 12; Output II: terminals 16, 17, 18; Output III: terminals 7-, 8 , 9-
    Output I, IIRelay output
    Contact loading253 V AC/2 A/500 VA/cos φ min. 0.7; 40 V DC/2 A resistive load
    Mechanical life2 x 107 switching cycles
    Output IIIAnalog output
    Current range-20 ... 20 mA
    Loadmax. 550 Ω
    Analog voltage output0 ... ± 10 V; output resistance 500 Ω (bridge between terminal 7 and 9)
    Analog current output0 ... ± 20 mA or 4 ... 20 mA; load 0 ... 550 Ω (terminals 7 and 8)
    Line fault detectiondownscale -21.5 mA (-10.75 V) or 2 mA (1 V), upscale 21.5 mA (10.75 V)
    Collective error messagePower Rail


    ConnectionPower Rail or terminals 23 , 24-
    Rated voltage20 ... 35 V DC
    Ripplewithin the supply tolerance
    Power consumptionmax. 3 W







    Connection sidefield side
    ConnectionInput I: terminals 1 , 2-; Input II: terminals 13 , 14-; Input III: terminals 15 , 14-
    Programmable Tare0 ... 500 of span
    Input ISignal, analog
    Input signal-100 ... 100 mV
    Input resistance> 1 MΩ for voltage measurement
    Input II, IIItare adjustment, calibration and zero
    Open circuit voltage/short-circuit current18 V / 5 mA
    Active/PassiveI > 4 mA/I < 1.5 mA



    1-channel isolated barrier, 24 V DC supply (Power Rail), Strain gauge b (full or half bridge), Output 0 mA ... ± 20 mA or 0 V ... ± 10 V, 2 relay contact outputs, Programmable high/low alarm, Configurable by PACTware or keypad, RS-485 interface, Line fault detection (LFD), Housing width: 40 mm, Number of channels: 1-channel, Trip relay, Rated voltage: 20 ... 35 V DC, Field device: strain gauge bridge, Type: 2 x relay (change-over contact), Signal: 1 x -20 ... 20 mA